Model |
TP-10KW |
TP-12KW |
TP-15KW |
TP-20KW |
TP-25KW |
TP-30KW |
TP-40KW |
||||||||
Input voltage |
380VAC±25%(3phase 4wires) |
||||||||||||||
Input frequency |
50HZ/60HZ±5% |
||||||||||||||
Charger current |
15A(max.) |
||||||||||||||
Rated power |
10KW |
12KW |
15KW |
20KW |
25KW |
30KW |
40KW |
||||||||
DC voltage |
192V/220V/240V/360V/384VDC |
240V/360V/384VDC |
|||||||||||||
DC voltage range |
DC192V(DC168V-DC240V)/ DC220V(DC189V-DC270V)/ DC240V(DC210V-DC300V) DC360V(DC315V-DC450V)/ DC384V(DC336V-DC480V) |
||||||||||||||
Output voltage |
380VAC±5%(3phase 4wires ) |
||||||||||||||
Output frequency |
50HZ/60HZ |
||||||||||||||
Output wave |
Pure sine wave |
||||||||||||||
Efficiency |
Loads 100%≥95% |
||||||||||||||
THD |
Liner loads<3%(full load),THD<5% |
||||||||||||||
Overload |
100-120% 30S; bigger than 120%,100MS |
||||||||||||||
Protection |
Overload, short circuit, over temperature, overpressure, low voltage, low battery, peak surge, phase sequence protection, etc. |
||||||||||||||
Battery type |
Sealed, maintenance-free lead acid |
||||||||||||||
Transfer time |
3S-5S |
||||||||||||||
Lcd display |
Inverter input voltage, frequency, output voltage, frequency, load percentage |
||||||||||||||
Communication function |
RS232/RS485 |
||||||||||||||
Operating environment temperature |
0-40℃ |
||||||||||||||
Storage environment temperature |
-15 - +50℃ |
||||||||||||||
Operating / storage environment relative humidity |
20-93% No condensation |
||||||||||||||
Altitude |
Below the altitude of 1000m the following (1% meters per 100 meters of power down 4000, the highest m) |
||||||||||||||
Appearance size: L* W * H (mm)(mm) |
750*580*920 |
||||||||||||||
Package size: L* W * H (mm)(mm) |
890*740*1180 |
||||||||||||||
Net weight/Gross weight(KG) |
160/180 |
170/190 |
190/210 |
220/240 |
230/250 |
250/270 |
330/350 |